200-amp underground service upgrade
& EV charger for a Woodland Hills home
The owners were renovating the whole house and adding an electric vehicle, and their 100-amp service was already maxed out. We replaced it with a new Siemens 200-amp panel on the existing underground feed, brought the grounding up to code and ran a dedicated circuit to a Level 2 charger in the garage. LADBS permit and LADWP meter set included.
A full renovation that outgrew a 100-amp service
The house is a one-story single-family home in Woodland Hills, served by an underground lateral from LADWP. The owners were renovating the entire house and planning new high-demand loads: kitchen appliances, future HVAC and an electric vehicle.
The original 100-amp panel had no room left, the grounding didn’t meet current code, and the service equipment needed replacing to take the new loads. Woodland Hills is in the City of Los Angeles, so the permit ran through LADBS and the meter work through LADWP.
What the homeowners needed
- Enough capacity for the renovation, future HVAC, kitchen appliances and EV charging at home
- Grounding and bonding that meet current code
- A Level 2 EV charger in the garage on its own circuit
- No digging up the yard. The existing underground conductors had to stay in service
The existing electrical system
The house was still running on its original 100-amp meter and main, fed underground from LADWP. It was enough for the house as built, not for the house after the remodel.
- ✓ 100-amp meter/main with no open spaces
- ✓ Underground lateral and conduit from LADWP
- ✓ Grounding that didn’t meet current code
- ✓ No circuit available for an EV charger
New service, new grounding, new EV circuit
New Siemens 200-amp panel
Removed the 100-amp meter/main and installed a Siemens 200-amp, 40-space main-breaker panel rated for the underground feed.
Existing underground feed reused
Reconnected the new panel to LADWP’s existing underground conduit and conductors. No trenching, no yard excavation.
Grounding and bonding
Drove two 5/8″ × 8′ copper ground rods 6′ apart and bonded a #4 copper grounding electrode conductor to the rods and the main cold-water pipe.
60-amp EV charger circuit
Ran #6 copper in 3/4″ EMT to the garage and installed the Level 2 charger on its own dedicated breaker.
Permit, inspection and meter set
One LADBS electrical permit covered the panel and the EV circuit. LADWP handled service planning and set the new meter.
From permit to power back on
- 1Assessment. Confirmed the 100-amp service couldn’t carry the new loads, checked utility records for the underground lateral and picked a panel compatible with the existing feed.
- 2LADWP service planning. Submitted the service-planning paperwork and got the meter spot approved using the existing lateral conduit.
- 3LADBS permit. Pulled one electrical permit covering the service upgrade and the EV branch circuit, and gave the homeowners notice of the shutdown.
- 4Installation. De-energized and removed the old meter/main, mounted the Siemens panel, reconnected the underground conductors, installed the grounding and ran the EV circuit.
- 5Inspection and meter set. Passed the LADBS inspection, then LADWP set the new meter and energized the service.
Room to grow, and an EV that charges at home
Double the capacity
200 amps and 40 spaces leave headroom for the new kitchen, future HVAC and whatever comes next.
Level 2 EV charging
The garage charger runs on its own 60-amp circuit instead of sharing power with the rest of the house.
Code-compliant grounding
Two new ground rods plus the water-pipe bond, inspected and signed off by LADBS.
No yard excavation
The existing underground conduit and conductors were reused, so there was no trenching across the yard.
What changed
| Before | After | |
|---|---|---|
| Service | 100-amp meter/main | Siemens 200-amp, 40-space main-breaker panel |
| Utility feed | Underground lateral from LADWP | Same lateral, reconnected to the new panel |
| Grounding | Not up to current code | Two ground rods, #4 copper GEC, water-pipe bond |
| EV charging | No circuit available | Level 2 charger on a dedicated 60-amp circuit |
| Permit | None | LADBS permit, inspected and finaled |
Job photos
The actual job, not stock photos.
What the homeowner said
“We hired Branover when our usual electrician was not available. Michael was wonderful from the start, giving us the bid price that we had turned down and making recommendations that were helpful as well. Branover installed an upgraded electrical panel and an EV hookup in our garage. The work was done fast, accurately and neatly. They then came back to help us with electrical connections for our new dishwasher.
Sorry, former electrician. We are Branover customers from here on out!”